The system in which the neutral point is grounded through a current limiting device (resistor) is known as a resistance grounded system and the grounding is referred to as resistance grounding. This method is used when it becomes necessary to limit the earth fault current.
The resistor used in this grounding may comprise either wire or water column resistance and the value of resistance used is generally higher than the system reactance so as to limit the power loss in the resistor due to earth fault.
The value of resistance required for grounding purposes increases with the increase in operating voltage in order to limit the short circuit current during an earth fault. The resistance grounded system with earth fault at point F in phase B is shown above and its phasor diagram is shown in the below figure.
Where,- IC = Capacitive current
- √3IC = Capacitive current per phase
- 3IC = Resultant capacitive fault current
- IF = Fault current.
The current IF, IBR, and IBY will be flowing through fault point F in phase B. The phase angle of the fault current will depend upon the impedance at the fault point. The capacitive currents IBR and IBY will lag the voltages VBR and VBY respectively by 90°. The fault current IF is resolved into two components one is the reactive component IX and the other is the resistive component IR.
The resultant capacitive fault current will be in phase opposition with the reactive component at fault point F. This resultant capacitive fault current can be neutralized by adjusting the value of resistance R to a sufficiently low value. Resistance grounding is used for low voltage short-length overhead lines, as the charging currents in these lines are small.
If the earthing resistance is of low value (when Irea is equal to IC), the fault currents are high and the system condition approaches the solid earthing. On the other hand, if the earthing resistance is of higher value so that Irea is less than IC then the system conditions approach that of the ungrounded neutral system with the risk of transient overvoltages occurring.
The value of resistance is so chosen that at the time of an earth fault on any phase, a current equal to the full load current of the largest alternator or transformer feeding the system, flows in the earth connection. This will keep the overvoltages within limits which can be easily handled by the equipment and switch gears.